| MODEL NAME |
VGD-60K33 |
VGD-80K33 |
| CAPACITY |
60KVA/48KW |
80KVA/64KW |
| P.F. |
0.8 (on-line, double
conversion, multiprocessor control) |
| INPUT |
Voltage |
220V / 380V, 230V
/ 400V, 240V / 415V (3 Phase 4 Wire) |
| Input range |
+/- 15% |
| Frequency |
50Hz / 60Hz +/- 5% |
| Rectifier-Charger |
With soft start |
| PFC |
PF > 0.97 |
| OUTPUT |
Voltage |
220V / 380V, 230V
/ 400V, 240V / 415V (3 Phase 4 Wire) |
| Accuracy |
+/- 1% at steady
state.
+/- 2% at dynamic state (load fluctuations 100% ~
0% ~ 100%) |
| Frequency |
50Hz / 60Hz synchronized
+/- 4% , free running +/- 0.05% |
| Slew Rate |
+/- 1Hz/s |
| Waveform |
Sine-wave |
| Efficiency |
90% to 92% |
| Total Harmonic Distortion |
< 3% |
| Phase displacement |
120° +/-1% (balanced
load) , 120° +/-% (imbalances 50% of the load) |
| Dynamic recovery time |
10 ms, at 98% of
the state value |
| Admissible overload |
125% (10'), 150%
(1') |
| Amissible crest factor |
3:1 |
| Imbalance output voltage with
load 100% unbalanced |
<2% |
| Static Bypass |
Type and activation |
Solid state |
| Voltage |
220V / 380V, 230V
/ 400V, 240V / 415V (3 Phase 4 Wire) |
| Frequency |
50 or 60Hz |
| Activation criterion |
Microprocessor control |
| Transfer Time |
Nil |
| Admissible overload |
400% for 10s, Short
circuit for 40ms |
| Passage to Bypass |
Immediate, for overloads
for over 160% |
| Manual Bypass |
Type |
Without interruption |
| Voltage |
220V / 380V, 230V
/ 400V, 240V / 415V (3 Phase 4 Wire) |
| Frequency |
50 or 60Hz |
| Batteries |
With batteries |
YES |
| Battery test |
YES, programmable |
| Communication |
RS-232/485 ports
as standard and AS-400 |
| Charger |
Technology |
PWM |
| Charging current |
0.2C |
| Float voltage |
13.6V |
| Recharging time |
From the end of back-up
time to 80% of the total charge 3 to 4 hours depending
on the power of the device (depending on type of batteries) |
| Environment |
Noise Level |
<60 dBA (at 1m.
distance and 100% load) |
| Operating temperature |
From 0° to 40°C |
| Protection UNE 2032478IR |
IP20 |
| Electromagnetic compatibility |
En50091-2 |
| Safty |
EN-50091-1, EN-60950 |
| Marking |
CE |
| Quality |
ISO-9001 |
| Connection |
By input / output
terminals |
| Dielectric rigidity |
2,500V AC for 1 min. |
| Ventilation |
Forced |
| Humidity |
Up to 95% without
condension |
| Maximum working height |
2,400 M s.n.m |
| Dimension DxWxH |
755 x 600 x 1255
mm |
| Weight (kg) |
770 |
TBA |