| MODEL |
|
BNT-400A |
BNT-400AP |
BNT-500A |
BNT-500AP |
| CAPACITY |
Capacity |
400VA |
500VA |
| OUTPUT |
Voltage (on battery) |
Simulated sine wave
at 100V / 110V / 115V / 120V or 220V / 230V / 240V
+/- 5% |
| Frequency (on battery) |
50 or 60 Hz +/-1Hz |
| Voltage Regulation( AVR) |
AVR automatically
increase output voltage 15% above input voltage if
-9% to -25% of nominal.
AVR decrease output voltage 13% below input voltage
if +9% to +25% of nominal |
| Transfer Time |
2 / 4 milliseconds,
including detection time |
| INPUT |
Voltage |
100V / 110V / 115V
/ 120V or 220V / 230V / 240V +/- 25% at line input |
| Frequency |
50 or 60 Hz +/- 10%
(auto sensing) |
PROTECTION & FILTERING |
Spike Protection |
480 Joules, 2ms |
| Unit Input |
Fuse for overload
& short circuit protection |
| Overload Protection |
UPS automatic power
off if overload exceeds 110% of nominal at 60 seconds
and 130% at 3 seconds |
| 10 Base-T Cable Port |
OPTIONAL |
YES |
OPTIONAL |
YES |
| Short Circuit |
UPS output cut off
immediately or input fuse protection |
| BATTERY |
Type |
Sealed, maintenance-free
lead acid batteries with 3-6 years typical lifetime |
| Typical Recharge Time |
6 hours (to 90% of
full capacity) |
Back-up Time
(a PC with 15" monitor) |
10 - 20 mins |
20 - 30 mins |
| Protection |
Auto discharge protection |
| PHYSICAL |
Net Weight kg (lbs) |
4.2 (9.2) |
4.5 (9.9) |
5.8 (12.8) |
6.1 (13.4) |
| Shipping Weight Kg (Ibs) |
4.6 (10.1) |
4.9 (10.8) |
6.3 (13.9) |
6.6 (14.5) |
| Dimension WxDxH (mm) |
97 x 260 x 135
(3.8"x10.2"x5.3") |
97 x 320 x 135
(3.8" x 12.5" x 5.3") |
| Input Inlet |
IEC 320 power inlet |
| Receptacles |
NEMA 5-15R(115V)
/ IEC 320 female appliance coupler (220V) |
| INTERFACE |
RS232 |
NO |
YES |
NO |
YES |
| ALARM |
Battery Back-up |
Slow beeping sound
(about 0.47 Hz) |
| Battery Low |
Rapid beeping sound
(about 1.824 Hz) |
| Overload |
Continuously beeping
sound |
| ENVIRONMENT |
Ambient Operation |
3,500 meters max,
elevation. 0-95% humidity non-condensing, 0-40 deg |
| Audible Noise |
<40dBA (1 meter
from surface) |
| Storage Condition |
15,000 meter max.
elevation |