| Model |
ICH-550 |
ICH-1000 |
| Capacity (VA / W) |
550VA / 330W |
1000VA / 600W |
| INPUT |
Voltage |
230 Vac |
| Voltage Range (V) |
Narrow : 170 - 280 ; Wide
: 90 - 280 |
| Frequency Range (Hz) |
50 or 60 hz +/- 10% (auto
sensing) |
| OUTPUT |
Voltage (V) |
Simulated sine wave at
220 +/-10% (DC MODE)
Sine wave follow I/P Voltage (AC MODE) |
| Frequency (Hz) |
50Hz or 60Hz +/-0.1Hz |
| Wave Form |
Simulated sine wave (DC
MOE)
Sine wave (AC MODE) |
| EFFICIENCY |
AC to AC |
> 95 % |
| DC to AC |
> 80% |
| TRANSFER TIME |
Bypass to Inverter (ms) |
7ms typical |
| Inverter to Bypass (ms) |
7ms typical |
| LINE / INV |
AC to DC |
Narrow : 264 - 287 |
Narrow: 264 - 287 |
| DC to AC |
Narrow 253 - 275 |
Narrow : 257 - 272 |
| AC to DC |
Narrow : 163 - 180 |
Narrow : 80 - 100 |
| DC to AC |
Narrow : 174 - 194 |
Narrow : 86 - 106 |
| LED DISPLAY |
Line Mode |
Green LED |
| Battery Mode |
Yellow LED |
| Battery Fault / Overload |
Red Led (1) |
| Over Temp |
Red Led (2) |
| PROTECTION |
Overload Protection |
UPS automatic shutdown
if over load exceeds |
| Short Circuit Protection |
UPS output cut immediately |
| Thermal Protection |
(1) Fan ON
(2) Over Temp. LED ON, 3 min later UPS cut-0ff |
| DC INPUT |
Voltage / Load |
24 Vdc (10 ~ 14.5 Vdc) |
24 Vdc |
| Voltage Range |
10 ~ 14.5 Vdc |
20 ~ 29 Vdc |
| CHARGER |
Charging Voltage |
13.7 |
27.4 |
| Charging Current |
8A |
5A |
| Over Charge Protection |
14.5 |
29 |
| COOLING |
Forced Air |
| WEIGHT |
Kg (lb) |
1.6 (3.52 lb) |
1.8 (3.96 lb) |
| DIMENSION |
W x D x H (mm) |
123 x 136 x 102 (4.8"
x 5.4" x 4.0") |
| AUDIBLE NOISE |
<40dBA (1 meter from
surface) |
| ENVIRONMENT |
Temperature |
0 - 40 deg C |
| Humidity |
0 - 95% humidity |