HOME > UPS Manufacturer > On-Line UPS > Power Generation Plant UPS > 80K/100K/120KVA

PGP 30K31/45K31/60K31
 

Intelligent, digitalized, and true galvanic isolation online design specially designed for Power Plants.

Features :

  • Double conversion on-line system
  • IGBT inverter design
  • UPS controlled by Digital Signal Processor (DSP)
  • True galvanic isolation
  • Cold start function (DC power on)
  • High resolution 320*240 dots graphs LCD display
  • Smart RS-232 or RS-485 communication port
  • Remote control panel (option)
  • Sine wave pulse width modulation (SPWM)
  • Pure sine wave output less than 3% THD
  • UPS status display on LED flowchart
  • 20KHz high frequency inverter
  • Versatile modular design
  • Generator compatible
  • Multi-function LCD display
  • IBM AS-400 interface communication port (option)
  • Short circuit and overload protection
  • Emergency power off function
  • Multiple language LCD display
  • On line output voltage selected
  • Anti-harmonic filters included (option)
  • Intelligent maintenance system

MODEL NAME PGP-80K31 PGP-100K31 PGP-120K31
CAPACITY 80KVA/64KW 100KVA/80KW 120KVA/96KW
P.F. 0.8
AC INPUT Phase 3 Phase 3 wire / 3 Phase 4 wire and ground
Voltage range 380V/220V or 208V/120V +/- 15%
Frequency range Auto-sensing, 50Hz / 60Hz +/-5Hz
Regulation Style 3 phase 6 pulses or 6 phase 12 pulses (option)
Efficiency of rectifier >97%
EFFICIENCY OF INVERTER >88%
TOTAL EFFICIENCY >85%
OUTPUT Phase Single phase
Voltage range 220V or 230V or 240V
Voltage regulation +/-1%
Transient state Return to 90% with 4 cycles
Overload capacity Bypass after 30 min while overload > 100% < 125%
  Bypass after 30 sec while overload = 125% < 150%
  Bypass after 30 cycles while overloadexceed >=150%
Frequency 50Hz / 60Hz
Frequency Regulation +/- 1%
Range of phase lock +/- 5Hz
Range of lock released > +/- 5Hz
Range of lock back +/- 3Hz
Wave Sine wave
Load crest factor 3 : 1
Total harmonic
distortion
Less 3% for linear load
STATIC SWITCH Transfer way When inverter and utility are synchronized at same phase and voltages, bypass to inverter
Transfer time Bypass to inverter 0ms
Normal state, inverter to bypass 0ms
Efficiency >99%
Frequency Stability +/- 0.5%
CHARGER Voltage DC410V
Current Current can be adjusted at 3A, 5A, 10A, 15A, 20A, 30A automatically
Charging period Return to 90% from 100% exhausted battery within 8 hours (depending on type of batteries)
UNIT Battery type Bank with 12V x 30pcs for DC410V version
Backup time Depending on type of batteries
Noise Less than 60dBA from the surface of 1m away
Environment Operating Temperature 0 - 40 deg.
Storage Temperature -25 ~ 55 deg.
Ambient operation 3,500 meters max. elevation, 0-95% humidity non-condensing
Physical size
W x D x H mm
WxDxH (mm) 1600 x 800 x 1800 (62.9" x 31.5" x 70.9")
Weight Net Weight (Kgs) 1588 (349.4 lb) none none