| Tower Model (LED display)
|
SMK-600A |
SMK-800A |
SMK-1000A |
SMK-1250A |
| Tower Model (LCD display)
|
SMK-600A-LCD |
SMK-800A-CD |
SMK-1000A-CD |
SMK-1250A-CD |
| 19" Rack-mount Model
|
SMK-600A-RM |
SMK-800A-RM |
SMK-1000A-RM |
SMK-1250A-RM |
| INPUT |
Capacity |
600VA |
800VA |
1000VA |
1250VA |
| Voltage |
+/-25% at line input,
single phase |
| Frequency |
50 or 60Hz +/-5Hz
(auto sensing) |
| OUTPUT |
Voltage
(on battery) |
Pure sine wave at
+/-5% of nominal, -10% of nominal after low battery
warning |
Frequency
(on battery) |
50 or 60Hz +/-0.5% |
| Voltage Regulation(AVR) |
AVR automatically
increase output voltage 15% above input voltage if
-9% to -25% of nominal.
AVR decrease output voltage 15% below input voltage
if +9% to +25% of nominal |
PROTECTION & FILTERING |
Spike Protection |
320 Joules, 2ms |
| Unit Input |
Fuse for 110V models
(600VA~2500VA) and 220V models (under 1250VA), breaker
for 110V model (3000VA) and 220V models (above 1500VA) |
| EMI/RFI filter |
10dB at 0.15MHz,
50 dB at 30MHz |
| Overload Protection |
UPS automatic shutdown
if overload exceeds 110% of nominal at 20 seconds
and 125% at 5 seconds. |
| Transfer Time |
2/4 milliseconds
(typical), including detection time |
| Short Circuit |
UPS output cut off
immediately or input fuse(or breaker) protection |
| BATTERY |
Type |
Hot swappable, sealed,
maintenance-free lead acid, with 3-6 years lifetime |
| Typical Recharge Time |
4 hours (to 90% of
full capacity) |
| Protection |
Automatic self-test
& discharge protection, Replace battery indicator |
Back up Time
(one PC and one 15" monitor) |
¡Ü 55 min |
¡Ü 60 min |
¡Ü 65min |
¡Ü 70min |
Net Weight Kg
(lbs) |
Tower |
13.8 (30.4 lb) |
14.5 (31.9 lb) |
15.0 (33.0 lb) |
15.8 (34.8 lb) |
| 19" 2U Rack-mount |
15.7 (34.5 lb) |
18.0 (39.6 lb) |
20.0 (44.5 lb) |
23.5 (51.7 lb) |
| 19" 3U Rack-mount |
N/A |
18.0 (39.6 lb) |
20.0 (44.5 lb) |
23.5 (51.7 lb) |
DIMENSION
W x D x H (mm) |
Tower |
140 x 436 x 210 (5.5"
x 17.2" x 8.3") |
| 19" 2U Rack-mount |
483 x 430 x 84 (19.0
"x 16.9" x 3.3") |
| 19" 3U Rack-mount |
483 x 381 x 130 (19.0"
x 15.0" x 5.1") |
| LCD Indicators |
Status |
Indicate line, bypass,
inv, backup, fault, bat capacity, load capacity, I/P
frequency, O/P voltage, O/P frequency, inside temperature,
fault statuts, load |
| INTERFACE |
RS232 |
Detect battery low,
Schedule UPS on/off, AC input/output power status
display. |
| Dry contact |
Sends AC fail and
battery low signals, and receives shutdown signal
from computer. |
| Option |
Novell, SNMP, Windows
NT, Windows 95/98/2000/ME |
| ALARM |
Battery Back-up |
Slow beeping sound
(about 0.25Hz) |
| Battery Low |
Rapid beeping sound
(about 1.00Hz) |
| Overload |
Continuously beeping
sound |
| ENVIRONMENT |
Ambient Operation |
3,500 meters max,
elevation. 0-95% humidity non-condensing, 0-40 deg |
| Audible Noise |
<40dBA
( 1 meter from surface) |
<45dBA
1m from surface |
| Storage Condition |
15,000 meter max.
elevation |