| Tower Model |
SXL-5100A |
| 19" Rack-mount Model |
SXL-5100A-RM (5U) |
| INPUT |
Capacity |
5100VA |
| Voltage |
+/-25% at line input, single
phase |
| Frequency |
50 or 60Hz +/-5Hz (auto sensing) |
| OUTPUT |
Voltage
(on battery) |
Pure sine wave at +/-5% of nominal,
-10% of nominal after low battery warning |
Frequency
(on battery) |
50 or 60Hz +/-0.5% |
| Voltage Regulation(AVR) |
AVR automatically increase output
voltage 15% above input voltage if -9% to -25% of
nominal.
AVR decrease output voltage 15% below input voltage
if +9% to +25% of nominal |
PROTECTION & FILTERING |
Spike Protection |
660 Joules (@10/1000µs) |
| Unit Input |
Fuse for 110V models except 3000A,
breaker for 3000A and 220V models |
| EMI/RFI filter |
10dB at 0.15MHz, 50 dB at 30MHz |
| Overload Protection |
UPS automatic shutdown if overload
exceeds 110% of nominal at 20 seconds and 125% at
5 seconds. |
| Transfer Time |
2/4 milliseconds (typical), including
detection time |
| Short Circuit |
UPS output cut off immediately
or input fuse(or breaker) protection |
| BATTERY |
Type |
Hot swappable, sealed, maintenance-free
lead acid (12V/17AH) |
| Typical Recharge Time |
4 hours (to 90% of full capacity) |
| Protection |
Automatic self-test & discharge
protection, Replace battery indicator |
| Battery Quantity |
6 pcs |
| Built in fast charger |
Nominal : 5.5A, 3.5A~8A adjustable |
| Back Up Time |
Tower Model |
Full Load |
9.5 ~10.5 mins |
| Half Load |
25 ~ 26 mins |
| 19" RM Model |
Full Load |
9.5 ~10.5 mins |
| Half Load |
25 ~ 26 mins |
Net Weight Kg
(lbs) |
Tower Model |
81.8 (179.9 lbs) |
| 19" Rack-mount |
81.8 (179.9 lbs) |
DIMENSION
W x D x H (mm) |
Tower |
710 x 214 x 428 (27.9" x
8.4" x 16.8") |
| 19" Rack-mount |
483 x 710 x 214 (19" x 27.9"
x 8.4") |
| INTERFACE |
RS232 |
Detect battery low, Schedule
UPS on/off, AC input/output power status display. |
| Dry contact |
Sends AC fail and battery low
signals, and receives shutdown signal from computer. |
| Option |
Novell, SNMP, Windows NT, Windows
95/98/2000/ME |
| ALARM |
Battery Back-up |
Slow beeping sound (about 0.25Hz) |
| Battery Low |
Rapid beeping sound (about 1.00Hz) |
| Overload |
Continuously beeping sound |
| ENVIRONMENT |
Ambient Operation |
3,500 meters max, elevation.
0-95% humidity non-condensing, 0-40 deg |
| Audible Noise |
< 45 dBA (1 meter from surface) |
| Storage Condition |
15,000 meter max. elevation |